Adjustable pusher arms
Two yoke-type arms set the high and low switching points to the span of level you want to control.
Two set points define where the controller should start and stop correcting the level. A small pneumatic valve then controls the output between those points.

Two set points define where the controller should start and stop correcting the level. A small pneumatic valve then controls the output between those points.
The valve is in the low level position when the liquid level is below the float and remains there until the float rises to the pre-set high level. The micro valve then reverses position until the float drops to the pre-set low level. The instrument is supplied with flange and grooved coupling for mounting, from the side of the tank.
Standard instruments are supplied with a three way micro valve and three 1/4" NPT ports; connections to the ports depend on the control action desired.
Two yoke-type arms set the high and low switching points to the span of level you want to control.
Three 1/4" NPT ports; the port connections determine the control action.
Intended for crude oil, oil and condensate service at specific gravity 0.6 to 1.2.
Supplied with flange and grooved coupling for mounting onto the vessel from the side.
Standard model; higher output on request
| Connection | 4" NB CS, ASTM A105 flange as standard in 150#, 300#, 600# |
|---|---|
| Mounting | Side |
| Enclosure | Die-cast aluminium, weatherproof to IP 65 |
| Service fluid | Crude oil / oil / condensate |
| Specific gravity | 0.6 to 1.2 |
| Float material and size | SS 316, 90 mm x 135 mm long |
| Distance | 415 mm (from flange to centre of float) |
| Differential | 400 mm (maximum), 150 mm (minimum) |
| Inlet and outlet connection | 1/4" NPT |
| Operating pressure | 15 Bar / 15 kg/cm² |
| Temperature | 100 °C |
| Supply pressure | 2 kg/cm² |
| Output | 1 kg/cm², 3 kg/cm², higher on request |
| Action | Direct (increase in level will increase output) · Reverse (increase in level will decrease output) |
Share the tank, medium, specific gravity, high/low set points and control-valve details. We will confirm the controller range and configuration.