Snap-acting float

Micro Valve Level Controller

Two set points define where the controller should start and stop correcting the level. A small pneumatic valve then controls the output between those points.

Micro Valve Level Controller
Max. differential
400 mm
Min. differential
150 mm
Operating pressure
15 kg/cm²
Temperature
100 °C
Overview

Simple control between two level points

Two set points define where the controller should start and stop correcting the level. A small pneumatic valve then controls the output between those points.

The valve is in the low level position when the liquid level is below the float and remains there until the float rises to the pre-set high level. The micro valve then reverses position until the float drops to the pre-set low level. The instrument is supplied with flange and grooved coupling for mounting, from the side of the tank.

Standard instruments are supplied with a three way micro valve and three 1/4" NPT ports; connections to the ports depend on the control action desired.

Adjustable pusher arms

Two yoke-type arms set the high and low switching points to the span of level you want to control.

Three-way micro valve

Three 1/4" NPT ports; the port connections determine the control action.

Oil and condensate duty

Intended for crude oil, oil and condensate service at specific gravity 0.6 to 1.2.

Side mounting

Supplied with flange and grooved coupling for mounting onto the vessel from the side.

Specifications

Standard model; higher output on request

Connection4" NB CS, ASTM A105 flange as standard in 150#, 300#, 600#
MountingSide
EnclosureDie-cast aluminium, weatherproof to IP 65
Service fluidCrude oil / oil / condensate
Specific gravity0.6 to 1.2
Float material and sizeSS 316, 90 mm x 135 mm long
Distance415 mm (from flange to centre of float)
Differential400 mm (maximum), 150 mm (minimum)
Inlet and outlet connection1/4" NPT
Operating pressure15 Bar / 15 kg/cm²
Temperature100 °C
Supply pressure2 kg/cm²
Output1 kg/cm², 3 kg/cm², higher on request
ActionDirect (increase in level will increase output) · Reverse (increase in level will decrease output)

Set the high and low points

Share the tank, medium, specific gravity, high/low set points and control-valve details. We will confirm the controller range and configuration.

  • Fluid, specific gravity and concentration
  • Flow or level range, and line size
  • Operating pressure and temperature
  • Material of construction and end connection
  • Output, display and area classification
WhatsApp