Set-and-forget accuracy
Factory set accuracy of ±5 mm, with 1, 2, 3 or 4 switching positions fixed in the guide pipe at order.
A float moves with the liquid and trips sealed reed switches at fixed heights. It is a simple way to get one or more high/low signals without putting a mechanism into the process.

A float moves with the liquid and trips sealed reed switches at fixed heights. It is a simple way to get one or more high/low signals without putting a mechanism into the process.
It consists of a guide pipe made from SS 304 / SS 316, a magnetic float of SS 316 that moves on the tube with rise and fall of level. Hermetically sealed reed switches are housed in the guide pipe. The switches can be fixed at any position throughout the length of the pipe; however, the position should be defined at the time of order as it cannot be changed at site.
Since it works on magnetic principle, there is no mechanical connection and hence the chances of any wear, tear or fluid contamination are eliminated.
Factory set accuracy of ±5 mm, with 1, 2, 3 or 4 switching positions fixed in the guide pipe at order.
Hermetically sealed reed switches inside the guide pipe, with no mechanical linkage into the process.
Widely used on diesel and furnace oil day tanks, vending machines, pumping stations and water tanks.
PC, PLC, DCS and alarm annunciator configurable. Use a relay control unit for high resistive or inductive loads.
Standard model; custom guide lengths and float dimensions to order
| Accuracy | +/- 5 mm |
|---|---|
| Float arrangement | Available in single and multiple floats |
| Switching | Reed switch operation, 1, 2, 3 or 4 different positions, hermetically sealed at pre-fixed positions in the guide pipe |
| Guide tube | SS 304 / SS 316 |
| Float material | SS 316 magnetic float |
| Process connection | 2" / 3" MS flanged connection as per ASA 150# or as per customer's requirement |
| Float hydro test | Floats are hydro tested to work at 15 kg/cm². Floats for higher pressure can also be supplied |
| Max. pressure | Up to 20 kg/cm² |
| Working temperature | 90 °C |
| Enclosure | IP65 / Ex-proof Gr. IIA and IIB. Flameproof or weatherproof connection box |
| Wiring | Can be wired directly with low load; use a control (relay) unit for high resistive or inductive loads |
| Configuration | PC / PLC / DCS, alarm annunciator configurable |
| Mounting options | Also available in external cage type. Side mounted bracket available for easy installation in open tanks and sumps |
Switch positions must be defined at the time of order, as they cannot be changed at site. Optional relay units are available for higher current ratings.
Share the tank height, medium, required switch points and connection. We will confirm the guide length, float and switch arrangement.